Specifications
Ridge Vents
When installed properly, all Air Vent products mentioned here comply with the net free area requirements of nationally recognized model codes, including those written by the International Code Council. In addition, the vents have product evalutation approvals from Dade County, Florida, ICC and TDI.
Please call 1-800-AIR-VENT to obtain code body information for a particular Air Vent product.
Here's an overview of the specifications for Air Vent's complete line of ridge ventilation products.
View the wide range of colors in which our products are available in our color chart.
| Product | Model | Description | Colors | Size | Net Free Area |
| ShingleVent II | SHFV203, 12" wide |
Shingle-over ridge vent |
Black, Brown, Gray, Charcoal |
4' | 18 sq. in. per ft. |
| ShingleVent II-9 | SHFV209, 9" wide |
Shingle-over ridge vent |
Charcoal | 4' | 16 sq. in. per ft. |
| ShingleVent II-7 | SHFVII-7, 7" wide |
Shingle-over ridge vent |
Charcoal | 4' | 16 sq. in. per ft. |
| ShingleVent II-9A | CLASH9CC, 9" wide |
Shingle-over ridge vent |
Charcoal | 4' | 16 sq. in. per ft. |
| ShingleVent II-7A | CLASH7CC, 7" wide |
Shingle-over ridge vent |
Charcoal | 4' | 16 sq. in. per ft. |
| Multi-Pitch FilterVent |
FV101 | Aluminum ridge vent |
Black, Brown, White, Gray, Mill, Bronze, Zinc, Copper |
10'* | 18 sq. in. per ft. |
| FV110 | Aluminum ridge vent |
Black, Brown, White, Gray, Mill, Bronze, Zinc, Copper |
8'* | 18 sq. in. per ft. | |
| VenturiVent Plus | VVP | Shingle-over ridge vent |
Black | 4' | 18 sq. in. per ft. |
| VenturiVent Plus™ with Nails NEW! |
VVPN | Shingle-over ridge vent with a bag of 30 3-inch ring shank nails taped to each 4-foot piece. |
Black | 4' | 18 sq. in. per ft. |
| Peak FilterVent | PVF152 | Aluminum peak vent for contemporary roof designs | Black, Brown, Gray, Bronze |
Venting Pack | 9 sq. in. per ft. |
| Flash FilterVent |
FFV162 | Aluminum vent for roof/wall junctions | Black, Brown, Gray, Bronze, Copper |
Venting Pack | 9 sq. in. per ft. |
| Utility FilterVent | UFV172 | Aluminum vent for specialty applications | Black, Brown, Gray, Bronze |
Venting Pack | 9 sq. in. per ft. |
| Tile/Shake FilterVent | TFV111 | Adapters cover ends of tile, shake or metal roofs available for all FilterVent products | Black, Brown, White, Gray, Mill |
Venting Pack | 18 sq. in. per ft. |
Venting packs contain four pieces plus two end plugs, three connector plugs and straps. Flash FilterVent includes four pieces of Supplemental Flashing.
Note: Venting packs can be shipped UPS, except Zinc and Copper.
* Also available in venting packs.
THE SIMPLE MATHEMATICS OF A BALANCED RIDGE VENTILATION SYSTEM
- According to most building codes, you need 1 square foot of ventilation for every 150 square feet of attic floor space.
- For new home construction that includes a vapor retarder, the minimum is 1 square foot of ventilation for every 300 square feet of attic floor space.
- If your vents are split between ridge vents and intake vents, the minimum requirement is also 1 square foot of ventilation for every 300 square feet of attic floor space.
To determine how many feet of net free area you need, use this formula:
| Square feet of attic floor space 300 |
= | Square feet of net free area needed |
| For example: | ||
| 1500 square feet of attic floor space 300 |
= | 5 square feet of free are a needed |
- To determine how many feet of ShingleVent® II, Multi-Pitch FilterVent® or VenturiVent Plus you need, use this formula:
- 1/2 net free area x 144 ÷ 18 = feet of ridge vent needed
- For example: 2.5 (based on net free area of 5 square feet) x 144 ÷ 18 = 20 feet of ridge vent needed
- To determine how many feet of Air Vent soffit vents you need, use this formula:
- 1/2 net free area x 144 ÷ 9 = feet of soffit vent needed
- For example: 2.5 (based on net free area of 5 square feet) x 144 ÷ 9 = 40 feet of soffit vent needed
- The following charts may be used to:
- 1. Determine how much net free area is needed to satisfy FHA requirements.
- 2. Balance your ridge vent system.
DETERMINING VENTILATION REQUIREMENTS
| Attic Square Footage |
Min. Net Free Area Required (if balanced between intake and exhaust) |
Min Length of Ridge |
|
| 1200 1500 1800 2100 2400 2600 3000 3300 |
4' 5' 6' 7' 8' 9' 10' 11' |
576" 720" 864" 1008" 1152" 1296" 1440" 1584" |
16' 20' 24' 28' 32' 36' 40' 44' |
Note: ShingleVent II and Multi-Pitch FilterVent provide 18" of net free area per linear foot.
INSTALLING A BALANCED RIDGE VENT SYSTEM
- Measure the square footage of the attic (length x width).
- Measure the length of the ridge.
- Refer to the chart above for required net free area and minimum length of ridge for attic square footage.
- Note: In most cases, the length of the ridge balanced with the same net free area of intake vents will satisfy FHA minimum standards and most building codes.
- Use the chart below to calculate the amount of intake vents that should be installed to balance your ridge vent system.
- Always install ridge vents from end to end across the entire ridge for best appearance and to provide maximum ventilation area.
- Hip roofs, dormers and T- or L-shaped roofs may require a specially designed ventilation system. For information, request a copy of Air Vent's Principles of Attic Ventilation.See Contact Us.
Balancing Your Ridge Vent System
| Length of Ridge | Linear Feet of Continuous Soffit Vent |
Number of Undereave Vents | ||
| 16" x 8" | 16" x 6" | 16" x 4" | ||
| 15' | 30 | 5 | 6 | 10 |
| 20' | 40 | 6 | 9 | 13 |
| 30' | 60 | 10 | 13 | 19 |
| 40' | 80 | 13 | 17 | 26 |
| 50' | 100 | 16 | 21 | 32 |
| 60' | 120 | 19 | 26 | 39 |
| 70' | 140 | 23 | 30 | 45 |
| 80' | 160 | 26 | 34 | 51 |
| 90' | 180 | 29 | 39 | 58 |
Note: FHA requirements and most building codes state the minimum required net free area. This minimum ventilation area may not be enough to effectively ventilate the attic to prevent moisture damage and cool the attic enough in the winter to prevent ice dams.